Atmospheric air at 3 kg/s (dry basis) enters a cooling/dehumidifying coil with enthalpy 85 kJ/kg dry air and humidity ratio 19 g/kg dry air, and leaves with enthalpy 43 kJ/kg dry air and humidity ratio 8 g/kg dry air. The condensate leaves with enthalpy 67 kJ/kg. The required cooling capacity of the coil in kW is

  • A75.0
  • 123.8
  • C128.2
  • D159.0

Explanation

Condensate flow=3(0.019-0.008)=0.033 kg/s. Q_removed=ṁda(h1-h2)-ṁcond·hcond=3(85-43)-0.033(67)=126-2.21≈123.8 kW.